CARLO GAVAZZI - 3-phase monitoring relay tor phase sequence and phase loss - Detects when all phases are present and have the cor- rect sequence - Knob-adjustable undevoltage detection - Measures its own power supply - Power supply range: 208 to 240 and 380 to 480 VAC (=15%) - Output: 5 A SPDT relay normally energized - For mounting on DIN-rail in accordance with DIN/EN 50 022 - 17.5 mm DIN-rail housing (DIN 43880) - LED indication tor relay and power supply 0N Ordering Key DPA 53 C M23 Housing Function Type Item nu mber Output Power supply Output Specifications SPDT reiay, NE. 250 VAC Measures its own supply 5 A @ 250 VAC 5 A @ 24 VDC M48 320 to 430 VAC 25 A @ 250 VAC D013 2.5A@24VDC 30 x 108 operations 105 operations (at5 A, 250 V, cos (p :1) 7200 operations/h 2 WM) (ms) 4 kV (1.2/50 us) General Specifications Aiarm OFF delay < 300="" ms="" repeatability="" :="" 0.5%="" on="" full="" scale="" 45="" to="" 65="" hz="" a="" cha="" without="" notice="" (30.03="" 10p="" 1="">
Specifications aresubject to change without notice (30.03.10) 1
Monitoring Relays
3-Phase Sequence and Phase Loss
Type DPA53
Product Description Ordering Key
Housing
Function
Type
Item number
Output
Power supply
3-phase monitoring relay for phase
sequence and phase loss
Detects when all phases are present and have the cor-
rect sequence
Knob-adjustable undevoltage detection
Measures its own power supply
Power supply range: 208 to 240 and 380 to 480 VAC
(±15%)
Output: 5 A SPDT relay normally energized
For mounting on DIN-rail in accordance with
DIN/EN 50 022
17.5 mm DIN-rail housing (DIN 43880)
LED indication for relay and power supply ON
Type Selection
Mounting Output Supply: 208 to 240 VAC Supply: 380 to 480 VAC
DIN-rail SPDT DPA 53 C M23 DPA 53 C M48
Input
L1, L2, L3 Terminals L1, L2, L3
Measures its own supply
Measuring range
M23 160 to 240 VAC
M48 320 to 480 VAC
Hysteresis M23 3% on full scale
M48 4% on full scale
Input Specifications
Output SPDT relay, N.E.
Rated insulation voltage 250 VAC
Contact ratings (AgSnO2
Resistive loads AC 1 5 A @ 250 VAC
DC 12 5 A @ 24 VDC
Small inductive loads AC 15 2.5 A @ 250 VAC
DC 13 2.5 A @ 24 VDC
Mechanical life 30 x 106operations
Electrical life 105operations
(at 5 A, 250 V, cos ϕ=1)
Operating frequency 7200 operations/h
Dielectric strength
Dielectric voltage
2kVAC (rms)
Rated impulse withstand volt. 4 kV (1.2/50 µs)
Output Specifications
General Specifications
DPA 53 C M23
3-Phase relay for detection
of incorrect phase sequence
and phase loss.
Using the front knob it can
be decided the undervoltage
setpoint of the unit.
Supply range from 208 to
240 VAC and 380 to 480
VAC covered by two multi-
voltage relays. For mounting
on DIN-rail. Housing 17.5
mm wide suitable both for
back and front panel mount-
ing.
Power supply
Overvoltage cat. III
Rated operational voltage (IEC 60664, IEC 60038)
through terminals: L1, L2, L3
M23 208 to 240 VAC ± 15%,
45 to 65 Hz
M48 380 to 480 VAC ± 15%,
45 to 65 Hz
Rated operational power
M23
7 VA@230 VAC, 50 Hz
M48
13 VA@400 VAC, 50 Hz
Supplied by L1 and L3
Supply Specifications
Reaction time
Alarm ON delay < 100 ms
Alarm OFF delay < 300 ms
Accuracy (15 min warm-up time)
Temperature drift ± 1000 ppm/°C
Repeatability ± 0.5% on full scale
Indication for
Power supply ON LED, green
Relay ON LED, yellow
CARLO GAVAZZI Slorage Lemperamre -an to +an°c, R.H. < 95%="" malerial="" pass="" or="" noryl="" acc.="" to="" iec="" 60947="" level="" sefling="" ccc="" (gb14048.5)="" operation="" diagrams="" li="" v—|_l="" l2="" \="" l3="" \="" l2="" u="" l="" l2l="" l3="" l3="" l="" l1="" l="" “9'“="" on="" w="" v—\="" l3="" {77="" l3="" {77="" l2="" —="" l2="" —="" l1="" 7="" u="" 7="" m4="" l1="" l2="" l3="" 12="" 14="" m="" l1="" l2="" l3="" «2="" 14="" u:="" u\="" n="" hi="" u\="" l3="" 11="" l3="" spemncauons="" ar="">
2Specifications aresubject to change without notice (30.03.10)
DPA53
Mode of Operation
DPA53 monitors its own
3- phase power supply.
The relay operates when all
the phases are present, the
phase sequence is correct
and each phase-phase volt-
age is above the adjusted
setpoint. The relay releases
when one phase-phase volt-
age drops below the set-
point or when the phase
sequence is incorrect.
Example 1
The relay monitors that the
power supply has the cor-
rect phase sequence and
that all phases are present.
Example 2
The relay releases in case of
interruption of one or more
phases, provided that the
regenerated voltage does
not exceed the set voltage.
Operation Diagrams
L1
L2
L3
L2
L1
L3
L3
L2
L1
L1
L2
L3
Relay ON
Environment
Degree of protection IP 20
Pollution degree 2
Operating temperature
@Max. voltage, 50 Hz -20 to +60°C, R.H. < 95%
@Max. voltage, 60 Hz -20 to +50°C, R.H. < 95%
Storage temperature -30 to +80°C, R.H. < 95%
Housing
Dimensions 17.5 x 81 x 67.2 mm
Material PA66 or Noryl
Weight Approx. 75 g
Screw terminals
Tightening torque Max. 0.5 Nm
acc. to IEC 60947
Product standard EN 60947-5-1
Approvals UL, CSA
CCC (GB14048.5)
CE Marking L.V. Directive 2006/95/EC
EMC Directive 2004/108/EC
EMC
Immunity According to EN 61000-6-2
Emissions According to EN 61000-6-3
General Specifications (cont.)
Level setting
Select the proper undervolt-
age level using the knob
according to the phase-
phase voltage and the need-
ed sensitivity.
Centre knob:
Setting of under level on
absolute scale.
Hysteresis
Min {L1, L2, L3}
Set level
Power supply
Relay ON
Wiring Diagrams
Example 1 Example 2
CARLO GAVAZZI
Specifications aresubject to change without notice (30.03.10) 3
DPA53
67.2
18.7
45
17.5
81
2
Dimensions

Products related to this Datasheet